Transformer Stations
A transformer station is the plant's MV/LV station: the transformer itself, the medium-voltage ring main unit that connects it to the grid, the low-voltage switchgear the inverters feed into, and the station's own climate and protection supervision. Where a plant's data logger reports its stations, Mirox follows each one as a component of its own. A plant whose loggers report none shows nothing of this.
What a Transformer Station Is in Mirox
Like an inverter, a transformer station is a flat component of the solar plant, discovered automatically from the data logger that reports it — you do not enter stations by hand (though you can add one manually where no logger reports it). A station is identified by its serial number, never by its name: two stations on one plant may well carry the same name, and a renamed station keeps its history.
The station's low-voltage cabinets — the feeders the inverters hang on, lettered A, B, … as the station itself letters them — are not components of their own. Every low-voltage series carries the cabinet as a label, so a graph shows one line per cabinet. Which inverters feed which cabinet is not something the logger knows; it is left to you as an optional note on the station.
Mirox records these series per station:
| Series | Scope | What it tells you |
|---|---|---|
| Active power | per cabinet | What the cabinet carries now (W); positive = PV power leaving towards the grid, negative = the station drawing from the grid, as at night |
| Reactive power | per cabinet | The cabinet's reactive power (var) |
| Power factor | per cabinet | cos φ of the cabinet |
| Voltage | per cabinet, per phase pair | Line voltages on the low-voltage side (V) |
| Current | per cabinet, per phase | Phase currents on the low-voltage side (A) |
| Exported energy | per cabinet | The cabinet's lifetime counter of energy that left towards the grid (Wh) |
| Imported energy | per cabinet | The cabinet's lifetime counter of energy drawn from the grid (Wh) |
| MV current | per phase | The transformer's medium-voltage side currents (A) |
| Frequency | station | Grid frequency at the station (Hz) |
| Oil temperature | station | The transformer's oil temperature (°C) |
| Temperature and humidity | per room | Climate in each low-voltage cabinet and in the medium-voltage room |
| Operating state | station | The platform's standard state, the same scale as inverters, trackers and wind turbines |
| Condition flags | station | The station's switchgear positions and protection signals packed into one word |
The energy counters are the station's own and survive any restart of the monitoring; Mirox never derives a station's energy from its power.
What the operating state means
| The station is … | Operating state |
|---|---|
| energised, with at least one low-voltage cabinet closed | Producing |
| de-energised by an open breaker, disconnector or load switch — opened by hand or by remote command | Stopped by command |
| tripped: a protection acted, a breaker opened on a fault, the transformer raised gas, oil level, oil temperature or pressure, or the emergency stop was pressed | Fault |
| not delivering a record | no state — a gap, never a value |
The condition flags
The condition word has one fixed bit per condition, the same on every plant and every maker. A healthy, energised station reads zero. The conditions: supervision offline; MV breaker open; MV disconnector open; MV earthing switch closed; ring main unit incoming line open; ring main unit outgoing line open (normal on the last station of a ring); low-voltage cabinet A open; low-voltage cabinet B open; a low-voltage breaker tripped on a fault; a transformer protection acted; Buchholz gas; oil temperature high; oil level abnormal; pressure relief valve acted; a door open; smoke; a surge protective device failed; emergency stop pressed; ring main unit insulation gas pressure low; a cabinet's supervision power supply shut down; MV switch control loop disconnected; a smoke sensor fault. How the series are named and decoded for your own dashboards is listed under Metric Collection — Transformer Station Metrics.
What the Pages Show
The Transformer stations page
A solar plant with transformer stations gets a Transformer stations entry in its left-hand navigation. The page holds:
- a summary row — the number of stations, the low-voltage active power of all of them together, the highest oil temperature and how many stations currently carry a set condition;
- one graph with a metric toggle — Power, Reactive power, Exported energy, Voltage, Current, MV current, Frequency, Oil temperature, Temperature, Humidity — drawing one line per station, and per cabinet, phase or room where the series carries one, over the time range you pick;
- the station table: the station's name with its serial, its model and rated power, the active power of each cabinet, the oil temperature, the set conditions, the operating state and when it last reported. The row menu opens the station's details, its edit dialog and, with the permission to create tickets, Create Ticket for that station.
The details show the nameplate as the logger reports it (model, manufacturer, firmware, rated power), the linked datasheet, the live values per cabinet and the serial numbers of the station's supervision units. The edit dialog lets you rename the station, hide it, mark it as needing attention, add a note and pick its datasheet. Hidden stations are left out of this page.
Components page
On a plant with transformer stations, the Components section has a Transformers tab with the same table, searchable, sortable, paged, and with the Show Hidden switch.
Datasheets
Transformer stations have their own entry in the component catalogue under Solar → Transformers: manufacturer and model, the rated apparent power, the medium- and low-voltage side voltages, the vector group, the short-circuit impedance, the no-load and load losses, the cooling class and the number of low-voltage windings, plus the manufacturer's PDF. A station discovered by a logger is linked to its datasheet automatically when the catalogue holds the exact model and manufacturer the logger reports; otherwise you pick the datasheet in the station's edit dialog. The datasheet is shared across every plant that uses the same station type.
Events
When the platform's view of a plant's transformer stations changes — a new station, a changed nameplate — or someone creates, edits or deletes one, the change is recorded under the Components category. Deleting a station breaks its history and is recorded at the Very high level. Events on a station open the Transformer stations page, and a station can be linked to tickets like every other component. Alarms derived from the station's protection signals — a trip, gas, oil or smoke as a judged event with a notification — are the next step and are not raised yet; the condition flags already show every signal live.
Data Collection
Transformer stations reach Mirox through the adapter of the logger that supervises them. The first fielded system is the Huawei Smart Transformer Station read through the Huawei SmartLogger it is connected to: the logger lists the station in its inventory, so a station is discovered the moment the logger is onboarded — nothing to configure. Other makers follow the same model. See the Data Scraper for how the edge agent collects and standardizes plant data.